Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/18/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) WE NEED A NEW GROUNDING ELECTRODE SYSTEM INSTALLED-2 GROUNDRODS 6' MINIMUM APART 2) FINISH STRAPING RISER 3) A PERMANENT METAL ADDRESS LABEL IS NEEDED 4) LABEL BREAKERS 5) USE CORRECT SIZED BREAKER FOR AMPACITY OF CONDUCTOR 6) INSULATION TO BE 1/4" INTO PANEL 7) A PERMIT WILL NEED TO BE OBTAINED FOR NEW WORK TO INTERIOR-ALL TRADES |