Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/30/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTIONS ARE COMPLETED. |
| 12/24/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WE CANNOT HAVE OPEN CONDUCTORS IN WALL. A SHEATHED CABLE RATED FOR 60 AMPS IS NEEDED 2) A GROUNDING FOR INTERIOR SUB PANEL IS NEEDED 3) PLEASE LABEL BREAKERS 4) PLEASE MAINTAIN WORKING CLEARANCES AS DISCUSSED |
| 12/18/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ |
| 11/21/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ NEED TO ISOLATE GROUND AND NEUTRAL AT SUB PANEL. USE BREAKERS LISTED ON PANEL BOARD ONLY. PLASTIC BUSHING IS REQUIRED AT 2" SLB. / A RE-FEE IS DUE BEFORE THE NEXT INSPECTION. ( REMOVED REFEE PER S.LONG ON 12/16/03) |
| 11/14/2003 |
ELECTRIC - FINAL |
|
Denied |
NEED TO INSTALL A SUB-PANEL TO REENERGIZE EXISTING CIRCUIT. USE PROPER WOOD SCREWS SUCH AS CAD. PLATED. A REFEE IS DUE BEFORE THE NEXT INSPECTION. |