Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/30/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ CORRECTIONS ARE COMPLETED.
12/24/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) WE CANNOT HAVE OPEN CONDUCTORS IN WALL. A SHEATHED CABLE RATED FOR 60 AMPS IS NEEDED 2) A GROUNDING FOR INTERIOR SUB PANEL IS NEEDED 3) PLEASE LABEL BREAKERS 4) PLEASE MAINTAIN WORKING CLEARANCES AS DISCUSSED
12/18/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/
11/21/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ NEED TO ISOLATE GROUND AND NEUTRAL AT SUB PANEL. USE BREAKERS LISTED ON PANEL BOARD ONLY. PLASTIC BUSHING IS REQUIRED AT 2" SLB. / A RE-FEE IS DUE BEFORE THE NEXT INSPECTION. ( REMOVED REFEE PER S.LONG ON 12/16/03)
11/14/2003 ELECTRIC - FINAL Denied NEED TO INSTALL A SUB-PANEL TO REENERGIZE EXISTING CIRCUIT. USE PROPER WOOD SCREWS SUCH AS CAD. PLATED. A REFEE IS DUE BEFORE THE NEXT INSPECTION.