Permit: T03EL02064

Parcel: 134101400


Addresses:

8112 E HAYNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
10/31/2003 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection 0000*
10/28/2003 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection 0245*/ NOTES: 1) BOND BUSHING REQUIRED AT 2" CONDUIT TERMINATION INTO CONCENTRIC KO, LOOSE LOCKNUT. 2) USE MIN. 1/4" BOLT TO SUPPORT RISER CONDUIT. #6 TEK SCREW NOT STRONG ENOUGH. 3) 2" CONDUIT STRAPS NEEDS TO BE SUPPORTED TO STRUCTURE WITH STRAPS AREAS AGAINST STRUCTURE.
10/27/2003 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection 0999*/ 1) PERMANENT ADDRESS REQUIRED ON SERVICE - NO MARKER. 2) GROUND ROD CLAMPS IN GROUND MUST BE BRASS TYPE. 3) NUETRAL MUST BE IDENTIFIED BY WHITE TAPE. 4) TIE-IN #2 FEEDER TO NEW SERVICE AND PROCEED AS POSSIBLE TO GET READY FOR CHANGE OVER. 5) BOND GAS LINE.