Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SHEET METAL SCREW NOT APPROVED FOR GROUNDING AT J-BOX - USE MECH LUG, NUT AND BOLT - SCRAPE OFF ENAMEL FOR GOOD CONTINUITY. 2) USE BUSHING IN BACK KO TO PROTECT WIRING. |
|
| 05/27/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ SUPPORT CONDUIT GROUND J-BOXES COMPLETE WIRING. | |
| 04/21/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* |