Permit: T03EL02036

Parcel: 132111120

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/07/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/10/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :/ 1) OK TO CLEAR INCREASE 2) CALL IN FOR FINAL INSPECTION AFTER TIE-IN
04/28/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) NOTES: MAXIMUM ALLOWED ANGLE FOR GROUND ROD IS 45 DEGREE PER ARTICLE 250 NEC.
04/26/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ EXPOSE GROUND RODS AND CLAMPS FOR INSP.
04/21/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ 1) GROUND RODS MUST BE 6' MIN. APART, PER ATR 250 NEC FLUSH WITH EARTH. 2) EACH SERVICE MUST BE CONNECTED TO BOTH GROUND RODS. 3) INSTALL PERMANENT ADDRESS LABELS, MUST BE SCREWED OR RIVITED TO ENCLOSURES. 4) BOND GAS PIPING 250-104. 5) USE MIN. ΒΌ" BOLTS TO SUPPORT RISER CONDUIT, DRYWALL SCREWS TOO SMALL.
03/17/2004 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*/ CANCELLED THRU OFFICE.