Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/10/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :/ 1) OK TO CLEAR INCREASE 2) CALL IN FOR FINAL INSPECTION AFTER TIE-IN | |
| 04/28/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) NOTES: MAXIMUM ALLOWED ANGLE FOR GROUND ROD IS 45 DEGREE PER ARTICLE 250 NEC. |
|
| 04/26/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ EXPOSE GROUND RODS AND CLAMPS FOR INSP. |
|
| 04/21/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*/ 1) GROUND RODS MUST BE 6' MIN. APART, PER ATR 250 NEC FLUSH WITH EARTH. 2) EACH SERVICE MUST BE CONNECTED TO BOTH GROUND RODS. 3) INSTALL PERMANENT ADDRESS LABELS, MUST BE SCREWED OR RIVITED TO ENCLOSURES. 4) BOND GAS PIPING 250-104. 5) USE MIN. ΒΌ" BOLTS TO SUPPORT RISER CONDUIT, DRYWALL SCREWS TOO SMALL. | |
| 03/17/2004 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection 0000*/ CANCELLED THRU OFFICE. |