Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/22/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO COVER INCREASE |
| 10/20/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* 1. SEE NOTES LAST INSP 2. BOND ALL NIPPLES, BOTH ENDS OF NIPPLES ON SUPPLY SIDE OF SERVICE 3. BOND GUTTER. |
| 10/16/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ NOTES: 1) BONDING BUSHING SUPPLY SIDE OF DISCONNECTS REQUIRE A LARGER GROUND WIRE. #6 CU. NOT BIG ENOUGH FOR 1000A SERVICES. SEE 250-66, 250-122 NEC. 2) CONT. TO BE ON SITE TO REMOVE GUTTER COVER FOR INSP. CONDUCTORS ENERGIZED. RECALL WHEN CONT. ON SITE TO MEET WITH INSPECTOR. |
| 10/15/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ NOTES: NEED PLANS/PERMIT ON SITE. |