Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL02025
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/22/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK TO COVER INCREASE | |
10/20/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1. SEE NOTES LAST INSP 2. BOND ALL NIPPLES, BOTH ENDS OF NIPPLES ON SUPPLY SIDE OF SERVICE 3. BOND GUTTER. | |
10/16/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ NOTES: 1) BONDING BUSHING SUPPLY SIDE OF DISCONNECTS REQUIRE A LARGER GROUND WIRE. #6 CU. NOT BIG ENOUGH FOR 1000A SERVICES. SEE 250-66, 250-122 NEC. 2) CONT. TO BE ON SITE TO REMOVE GUTTER COVER FOR INSP. CONDUCTORS ENERGIZED. RECALL WHEN CONT. ON SITE TO MEET WITH INSPECTOR. | |
10/15/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ NOTES: NEED PLANS/PERMIT ON SITE. |