Permit: T03EL02019

Parcel: 106042130


Addresses:

310 E MOHAVE RD #02

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/20/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) NOT TO BE CLEARED TILL INSIDE APPROVED
10/27/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
10/14/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0210*/ CORRECTIONS REQUIRED: 1) INSTALL PERMANENT ADDRESS ON METER SIDE OF SERVICE 2) REMOVE PAINT FROM COLD WATER PIPE WHERE CLAMPS ARE ATTACHED. WIRE BRUSH CLEAN 3) PUT SEALING TYPE LOCKNUTS ON EMT CONNECTIONS TERMINATED TO TOP OF PANEL. SEALING LOCKNUT MAY BE ON INTERIOR SIDE OF PANEL 4) THE EXISTING 200A METER/MAIN/LOAD CENTER HAS NEVER BEEN CUT-OVER BY TEP WHY? 5) THESE UNITS ARE DILAPIDATED AND UNINHABITABLE. ARE THESE UNITS VACANT DUE TO CITY ORDER ? 6) IF THESE UNITS ARE UNDER CITY ORDER TO NOT OCCUPY. WHAT IS PURPOSE OF NEW SERVICE GEAR ? CONTACT ME, MAC CAPISTRAN AT 909-5147