Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/20/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) NOT TO BE CLEARED TILL INSIDE APPROVED |
| 10/27/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/14/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*/ CORRECTIONS REQUIRED: 1) INSTALL PERMANENT ADDRESS ON METER SIDE OF SERVICE 2) REMOVE PAINT FROM COLD WATER PIPE WHERE CLAMPS ARE ATTACHED. WIRE BRUSH CLEAN 3) PUT SEALING TYPE LOCKNUTS ON EMT CONNECTIONS TERMINATED TO TOP OF PANEL. SEALING LOCKNUT MAY BE ON INTERIOR SIDE OF PANEL 4) THE EXISTING 200A METER/MAIN/LOAD CENTER HAS NEVER BEEN CUT-OVER BY TEP WHY? 5) THESE UNITS ARE DILAPIDATED AND UNINHABITABLE. ARE THESE UNITS VACANT DUE TO CITY ORDER ? 6) IF THESE UNITS ARE UNDER CITY ORDER TO NOT OCCUPY. WHAT IS PURPOSE OF NEW SERVICE GEAR ? CONTACT ME, MAC CAPISTRAN AT 909-5147 |