Permit: T03EL02001

Parcel: 131051040


Addresses:

5142 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/04/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000* SENT TO TEP ON 12/4AM
10/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) LEFT TOP ANGLED ENTRY NOT APPROVED. NON ACCESS ? FOR WIRE INSTALLATION OR REMOVE. ? DOWN TO CUSTOMER 1/2 OF SERVICE 2) TOP MISGHT STRAIGHT ENTRY, WIRING ENDS UP IN SAME WIREWAY AS UTILITY CONDUCTOR
10/16/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ UTILITY AND PREMISES WIRING MIXED IN COMPARTMENT. NEED PROPER ACCESS FOR TOP SIDE ENTRY INTO PANELBOARD. APPLY ALL OF YOUR ENTRIES IN THE PANELBOARD SECTION OF SERVICE.
10/13/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) USE BOTTOM PORTION OF SERVICE PANEL BOARD FOR BRANCH CIRCUIT WIRING 2) UPPER PORTION NOT ACCESSIBLE AND MIXING OF UTILITY WITH ? WIRING