Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/29/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) OK TO CLEAR FINAL |
| 03/15/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ PLEASE DRIVE GROUND ROD FLUSH OR BELOW GRADE. GROUND WIRE IS ON WRONG SIDE OF 'ACORN CLAMP'. I CANNOT WAIVE A CODE VIOLATION SUCH AS PENETRATING UTILITY SPACE. |
| 03/04/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED |
| 02/20/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CANNOT SEE WHERE YOUR SERVICE LOAD CENTER IS BONDED 2) LOAD CONDUCTOR CANNOT BE/GO THROUGH METER SPACE. THIS IS DEDICATED TO THE UTILITY SIDE ONLY. CANNOT HAVE WIRES MIXED (OWNER AND UTILITY) 230.7 3) NEED GAS BOND 4) CALL FOR OTHER A/C INSPECTIONS ON OTHER PERMIT |