Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/10/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST DERATE CONDUCTOR IN 1 1/4" CONDUIT 2) HAVE CITY APPROVED DERATING CALCULATION AND PANEL SCHEDULE RELATING TO CIRCUIT BREAKER ROLINGS 3) SEE LISTING-CANNOT ENTER THROUGH TOP OF PANEL BOARD 4) NOTE RENERGIZED WITH OUT CITY CLEARANCE |