Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL01918

Parcel: 11103014A


Addresses:

3761 E KLEINDALE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/18/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR 2) PLEASE ID HIGH LEG ORANGE
11/10/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PLEASE PROVIDE REJECTION PINS 2) TIGHTEN ALL TERMINATIONS 110.14 3) CLEAN SURFACE UNDER GROUND BAR 250.12 4) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8