Permit: T03EL01893

Parcel: 12712267A


Addresses:

5745 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL01893

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/09/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/1) THE NEW #4 BARE COPPER COMING FROM THE WATER LINE AND GROUND ROD NEED TO GO TO NUETRAL. THE WAY IT IS DONE NOW IT GOES TO THE ENCLOSURE ONLY - IF THE LUGS WERE A SINGLE DOUBLE LUG TYPE IT WOULD BE OK. 2) LIGHTS IN MAIN ROOM - ENDS SHOULD BE CAPPED OFF SO WIRING IS NOT SHOWING THRU END CAP.
10/01/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) HAVE LICENSED ELECTRICAL CONTRACTOR CONTACT ME BEFORE NEXT INSPECTION 218.0204 PGR 2) PLEASE COMPLETE #2 OF PREVIOUS INSPECTION 3) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED TERMINAL
09/25/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) FILL UNUSED OPENINGS IN BOX 2) WIRING METHOD FOR TRACK LIGHTING NOT TO CODE 3) PLEASE HAVE LICENSED L-11 ELECTRICAL CONTRACTOR PER FORM WORK 4) SERVICE DISCONNECT NEEDS GROUNDING ELECTRODE SYSTEM 5) INSTALL CORRECT SIZED GROUNDED CONDUCTOR 6) A PERMANENT METAL ADDRESS LABEL IS NEEDED 7) RE-SUPPORT CONDUIT BELOW DISCONNECT