Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/09/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) THE NEW #4 BARE COPPER COMING FROM THE WATER LINE AND GROUND ROD NEED TO GO TO NUETRAL. THE WAY IT IS DONE NOW IT GOES TO THE ENCLOSURE ONLY - IF THE LUGS WERE A SINGLE DOUBLE LUG TYPE IT WOULD BE OK. 2) LIGHTS IN MAIN ROOM - ENDS SHOULD BE CAPPED OFF SO WIRING IS NOT SHOWING THRU END CAP. |
| 10/01/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) HAVE LICENSED ELECTRICAL CONTRACTOR CONTACT ME BEFORE NEXT INSPECTION 218.0204 PGR 2) PLEASE COMPLETE #2 OF PREVIOUS INSPECTION 3) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED TERMINAL |
| 09/25/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) FILL UNUSED OPENINGS IN BOX 2) WIRING METHOD FOR TRACK LIGHTING NOT TO CODE 3) PLEASE HAVE LICENSED L-11 ELECTRICAL CONTRACTOR PER FORM WORK 4) SERVICE DISCONNECT NEEDS GROUNDING ELECTRODE SYSTEM 5) INSTALL CORRECT SIZED GROUNDED CONDUCTOR 6) A PERMANENT METAL ADDRESS LABEL IS NEEDED 7) RE-SUPPORT CONDUIT BELOW DISCONNECT |