Permit: T03EL01886

Parcel: 124060230


Addresses:

828 E 7TH ST #02


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T03EL01886

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2003 ELECTRIC - SERVICE UPGRADE Approved
09/26/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ 1) ADDRESS LABELS TO BE PERMANENTLY INSTALLED, BY RIVITS OR SCREWS TO ENCLOSURE, #9287 CITY OF TUCSON ORDINANCE ART 230-70 NEC. 2) GAS BONDING TO BE ATTACHED ON COSTUMER SIDE OF SHUT OF VALVE. PER 250-104 NEC. 3) SUPPORT BOX FOR GFCI OUTLET UNDER SERVICE PANEL 4) GROUND RODS TO BE DRIVEN FLUSH WITH FINISHED GRADE. PER 250-NEC 5) SUPPORT GAS BOND WIRE TO BLDG