Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL01874
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
12/12/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) PANEL SCHEDULE NEEDS TO BE MARKED. 2) BREAKER SLOT NEEDS COVER. 3) SUB-PANEL NEEDS TO HAVE GROUNDS AND NEUTRALS ISOLATED. CANNOT MIX IN SUB-PANEL. 4) OPEN ½" HOLE BOTTOM OF PANEL. 5) ALL DEVICE COVERS MISSING. 6) RECEPTACLE BELOW COOLER LOOSE. COOLER RECEPTACLE NOT ENERGIZED. |