Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 1006AM |
| 09/26/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) A RE-INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION 2) STILL CANNOT LOCATE GAS BOND 3) EQUIPMENT GROUND MUST BE SIZED PER 250-122. 70 AMP BREAKER TO SUB PANEL REQUIRES A NO. 8 AWG. CU. |
| 09/22/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) EQUIPMENT GROUNDING CONDUCTOR FOR 70 AMP BREAKER (TO SUB PANEL) REQUIRES A NO. 8 AWG CU. CONDUCTOR. 2) NEED GAS BOND 3) ISOLATE GROUNDS AND NEUTRAL. |