Permit: T03EL01873

Parcel: 134100120

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 1006AM
09/26/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) A RE-INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION 2) STILL CANNOT LOCATE GAS BOND 3) EQUIPMENT GROUND MUST BE SIZED PER 250-122. 70 AMP BREAKER TO SUB PANEL REQUIRES A NO. 8 AWG. CU.