Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO CLEAR INCREASE FOR UNITS 1 AND 2 |
| 09/22/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ NEED PROPER ADDRESS AND LABELS ON PERMIT SERVICE ENCLOSURES. |
| 09/19/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) THIS PERMIT IS FOR ONE SERVICE, TWO ON SITE. 2) SERVICES MUST BE ADDRESSED. 3) 3/4" EMT ENTRY ON TOP SIDE MUST BE HUB OR SEALING LOCKNUT. 4) WATER BOND? - YOU HAVE STEEL WATER LINES IN HOUSES. 5) WIRING TO INSIDE REPLACED OR REWIRED. - YOU NEED PERMITS. 6) BOTH RISER REQUIRE 2 SUPPORTS ONE ONLY HAS ONE. 7) SINCE THIS IS TEMPORARY TIED IN POWER - FINISH THIS UPGRADE AS SOON AS POSSIBLE. 8) EXPOSE GROUND ROD CLAMPS. |