Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/22/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 09/19/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 09/17/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) SERVICE REQUIRE A PERMANENT ADDRESS TAG, NO MARKER ALLOWED 2) THE RISER IS REQUIRED TO BE 2" RIGID OR IMC PIPE 3) THE GROUNDING SYSTEM FOR THE SERVICE REQUIRES 2-GROUND RODS 6' APART PLUS A WATER AND GAS LINE BOND 4) THE CHASE NIPPLE IN J-BOX ATTACHING TO THE 1" RIGID COUPLING IS NOT APPROVED FOR THAT USE IT MUST BE A CLOSED NIPPLE WITH A LOCK NUT ON INSIDE AND LOCKNUT OUTSIDE 5) RISE MUST HAVE A ROOF JACK ON TOP OF ROOF AND CEMENTED WITH ROOF COMPOUND 6) THE RISE MUST HAVE A SUPPORT BELOW ROOF WITH AT LEAST 1/4" ANCHORING MATERIAL 7) 1" CONDUIT MUST HAVE ONE SUPPORT 8) 1/2" CONDUIT BELOW MUST HAVE ONE SUPPORT |