Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP 1015AM |
| 10/06/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FINISH ITEMS #3, 4, 5 AND 10 OF PREVIOUS INSPECTION |
| 10/02/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920*/ 1) LOCKED-NO ACCESS |
| 09/16/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) PLEASE VERIFY GROUNDING ELECTRODE SYSTEM AND GAS AND WATER BONDS 3) LABEL ALL BREAKERS 4) WHAT ARE EXPOSED CONDUCTORS NEXT TO PANEL FOR 5) FILL UNUSED OPENING IN BACK OF PANEL 6) PLEASE VERIFY PERMIT FOR NEW A/C UNIT 7) A GUY BACK BRACE MAY BE NEEDED 8) ANTI-OXIDE COMPOUND NEEDED FOR ALUMINIUM CONDUCTORS 9) NEUTRALS TO BE 1 PER TERMINAL 10) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS LABEL |