Permit: T03EL01844

Parcel: 123053180


Addresses:

2350 E EDISON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/01/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) CABLE AND PHONE NOT TO STUD UP INTO DEDICATED COOCKING SPACE 110.26 2) WIRING IN KITCHEN HAS BEEN COVERED WITHOUT INSPECTION (NEW WIRING)
09/19/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SENT TO TEP ON 0922AM 1) COMPLETE #2 OF PREVIOUS INSPECTION AS DISCUSSED 2) FINISH WIRING OF ELECTRIC
09/17/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) Use manufactures approved hub below for riser. Hub should cover entire hole/openings 2) Conductors larger of #8 to be stranded 310.3