Permit: T03EL01826

Parcel: 123051680


Addresses:

2300 E WAVERLY ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/09/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*SENT TO TEP ON 1010AM
10/01/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) MAINTAIN WORKING SPACE IN FRONT OF PANEL 2) INSTALL ALL STRANDS UNDER TERMINAL LUG 3) FINISH INSTALLATION OF ALL BREAKERS 4) FILL UNUSED OPENING IN PANEL 5) TIGHTEN LOOSE FITTINGS 6) BOND WATER ON INTERIOR SIDE OF VALVE 7) USE AN APPROVED JUNCTION BOX FOR SPLICING CONDUCTORS TO FESTOON LIGHTING
09/30/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) HERE 10:10 AM, NO ANSWER AT DOOR. PLEASE RECALL AND LEAVE MESSAGE