Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL01820
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 09/23/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 09/17/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 09/10/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ NOTES: NO ANSWER AT DOOR. 1) MUST MAINTAIN WORKING CLEARANCE, DEDICATED SPACE OF 36" IN FRONT OF SERVICE EQUIP. 110-26 NEC. 2) NEED TO VERIFY INSTALLATION OF 2 GROUND RODS MIN. 6' SPACING. 3) NEED TO VERIFY GAS AND WATER PIPE BONDING. |