Permit: T03EL01820

Parcel: 130110690


Addresses:

1926 S MIRAMONTE SV


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL01820

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
09/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
09/23/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
09/10/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ NOTES: NO ANSWER AT DOOR. 1) MUST MAINTAIN WORKING CLEARANCE, DEDICATED SPACE OF 36" IN FRONT OF SERVICE EQUIP. 110-26 NEC. 2) NEED TO VERIFY INSTALLATION OF 2 GROUND RODS MIN. 6' SPACING. 3) NEED TO VERIFY GAS AND WATER PIPE BONDING.