Permit: T03EL01820

Parcel: 130110690


Addresses:

1926 S MIRAMONTE SV


Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T03EL01820

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Denied

Date Description Inspector Results Comments
09/23/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
09/23/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
09/17/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) DENIED-WEST GROUND ROD CAMP WROUT USE SAME TYPE AS ONE UDNER SERVICE (A CORN CLAMP) 2) THE GROUND WIRE ON THE ROD BELOW SERVICE MUST BE ON WEDGE SIDE 3) CANNOT VERIFY WATER OR GAS BOND