Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 1009AM |
| 09/30/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) NOTES: MUST HAVE PERMANENT ADDRESS LABEL SCREWED OR RIVITED TO ENCLOSURE. MARKER PEN NOT ACCEPTABLE. #9287 CITY OF TUCSON ORDINANCE 2) FRONT COVER INSIDE PANEL COVERING BREAKERS NOT CORRECTLY INSTALLED. THERE SHOULD BE NO GAPS BETWEEN COVER AND BREAKERS, POSSIBLE MANUFACTURERS DEFECT. CORRECT AND RECALL INSPECTION. 3) BOND GAS AND WATER PIPING 4) GROUND RODS MUST BE MINIMUM 6' APART. LEAVE NAME AND PHONE # OF C-11 LICENSED CONTRACTOR DOING WORK |