Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/01/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OWNER OR CONTR. TO HAVE TOP RESEAL UTILITY COMPARTMENT |
| 09/22/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*/ DID NOT PAY REFEE. |
| 09/18/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*/NOTES: 1) NO COMPLIANCE WITH INSP. 9/9/03, ART 230.7 NEC. 2) CONDUCTORS INSTALLED FROM ONE SERVICE PANEL RUNNING THROUGH ANOTHER NOT ALLOWED. 225.35, 225.40, 230.72C NEC., 225.37, 240.24. 3) ALSO CIRCUIT BREAKERS MUST BE IDENTIFIED. 4) GROUND WIRE IS A TRIP HAZARD. / A REINSPECTION FEE IS ASSESED. PLEASE PAY REFEE AT 201 N. STONE AV PRIOR TO FUTURE INSP. |
| 09/16/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/1) CALLED PHONE NUMBER PER MSG. NO ANSWER. NO COMPLIANCE WITH LAST INSP. A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO COMPLIANCE. |
| 09/09/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ NOTES: REMOVE BRANCH CIRCUITS INSTALLED THRU UTILITIES TERMINATION SECTION OF SERVICE ENCLOSURE, IN VIOLATION OF N.E.C. ARTICLE 230. |