Permit: T03EL01806

Parcel: 110030890

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL01806

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 11/18AM
11/14/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/06/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) SPLICE/TAP INSTALLATION TO BE EQUAL TO ORIGINAL 110.14 2) ANTI-OXIDE COMPOUND TO BE ON CONDUCTOR UNDER TERMINATION NOT APPLIED TO SURFACE 4) REPLACE STRIPPED OUT GUTTER SCREWS
11/05/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
10/28/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) GUTTER SEAL TO BE WITH METAL EQUAL TO GUTTER THICKNESS 2) BONDING JUMPER TO BE SIZED PER CODE 250.102 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 4) CLEAN SURFACE UNDER LUG 250.12 5) USE APPROVED CONNECTOR FOR ALUMINUM TO COPPER CONNECTIONS 110.14 6) SPLIT BOLT ONLY LISTED FOR 2 CONDUCTORS A RUN A TAP 110.3 7) GROUNDED CONDCUTOR TO BE OF COLOR ENTIRE LENGTH 200.6 8) YOU HAVE LOOSE CONDUCTOR TERMINATIONS 9) LABEL BREAKERS 10) ANTI OXID COMPOUND NEEDED AT ALUMINUM TERMINATIONS
10/10/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) UNDERGROUND COVERED WITHOUT INSPECTION 2) PERMANENT ADDRESS LABELS REQUIRED ON ALL METERS 3) 2002 NEC 250.24 EACH SERVICE SHALL HAVE GROUNDING ELECTRODE CONDUTCOR CONNECTED TO THE GROUNDED SERVICE CONDUCTOR. THE #4 COMING FROM THE GOURND RODS ONLY CONNECTS TO GUTTER INCLOSURE 4) 2002 NCE 250.92 BONDING AT SERVICES, DOES NOT ALLOW GROUNDING BY MEANS OF A STANDARD LOCK NUT AS WHERE OFF SET NIPPLES ENTER BOTTOMS OF METERS AND BOTTOMS OF GUTTER. WHERE THERE ARE UNPROTECTED CONDUCTORS A HEAVIER TYPE OF GROUNDING OTHER THAN A LOCK NUT IS REQUIRED 5) IN ATTEMPTING TO REMOVE GUTTER COVER ONE OF THE KEARNEY SPLICES FLASHED TO COVER. NEED TO RETAPE AND SEAL GUTTER HOLE 6) OVER HEAD TEP CONDUCTORS SUBJECT TO TEP ARPPROVAL