Permit: T03EL01799

Parcel: 134070520

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/12/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/08/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ CHANGE RECEPTACLE AT POOLSIDE TO GFSI. NEED DEAD FRONT COVER FOR SERVICE. ELIMINATE ADDED CIRCUITS (TOP OF SERVICE). STORAGE ROOM WIRING - A. ELIMINATE DRYER. B. INSTALL OTHER IN CONDUIT.
09/05/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*