Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/29/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/27/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) INSTALL MAIN BONDING JUMPER AS PER CODE OR USE KITCHEN ? 2) STRAP GROUNDING ELECTRODE CONDUCTOR TO PEDISTALL 3) PLEASE PROVIDE INFORMATION REQUESTED ON PREVIOUS INSPECTION #1 |
| 10/15/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE NAME OF ELECTRICAL CONTRACTOR. 2) TWO GROUND RODS REQUIRED - MUST BE 6' APART WITH A #4 BC GROUND UNSPLICED FOR 200A SERVICE AND STRAP. 3) JUMPER BETWEEN NUETRAL AND GROUND TO BE INSTALLED - KIT IS IN PEDISTAL. 4) CANNOT FINAL UNTIL STATE STICKER INSTALLED AT SERVICE CLEARING BLDG. 5) INSTALL ALL SCREWS ON COVER. |