Permit: T03EL01788

Parcel: 122180900


Addresses:

3626 E LEE ST M2

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/29/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/27/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) INSTALL MAIN BONDING JUMPER AS PER CODE OR USE KITCHEN ? 2) STRAP GROUNDING ELECTRODE CONDUCTOR TO PEDISTALL 3) PLEASE PROVIDE INFORMATION REQUESTED ON PREVIOUS INSPECTION #1
10/15/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) PROVIDE NAME OF ELECTRICAL CONTRACTOR. 2) TWO GROUND RODS REQUIRED - MUST BE 6' APART WITH A #4 BC GROUND UNSPLICED FOR 200A SERVICE AND STRAP. 3) JUMPER BETWEEN NUETRAL AND GROUND TO BE INSTALLED - KIT IS IN PEDISTAL. 4) CANNOT FINAL UNTIL STATE STICKER INSTALLED AT SERVICE CLEARING BLDG. 5) INSTALL ALL SCREWS ON COVER.