Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL01783

Parcel: 131080960


Addresses:

6021 E 26TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/23/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR 2) SENT TO TEP ON 02/24/04AM
02/04/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) SERVICE REQUIRES PERMANENT ADDRESS TAG 2) GAS BOND MISSING 3) SERVICE SHOULD NOT BE ABOVE GAS METER, CALL ME 4) EXISTING 30 2P, 40 2P, 50 2P AND 60 2P TOO MUCH FOR 100 AMP SERVICE