Permit: T03EL01778


Addresses:

217 N EUCLID AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/19/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 0922AM
09/18/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ THE GROUNDING ELECTRODE CONDUCTOR MUST RUN UNBROKEN TO THE SYSTEM. GROUNDED (NEUTRAL) CONDUCTOR FIRST. SEE NEC 250. THE BONDING OF THE CABINETS AND PIPES IS SECOND. THE 2-1/2" PIPE NIPPLE MUST BE PROPERLY TERMINATED TO THE METER CAN. THIS MEANS LOCKNUTS TOP AND BOTTOM MUST BE USED. CORRECT AND RECALL.