Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 1010AM | |
| 09/11/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ REFASTEN SERVICE AND BOX TO WALL. TIGHTEN WATER BOND CONNECTION. CONDUIT CROOKED AND LOOSE FITTINGS. STRAP CONDUIT. REROUTE #4 AWG CU. WATER BOND TO STRUCTURAL WALL, THEN TO CLAMP. NEED SEALING LOCK NUT AT SIDE OF PANEL. NEED PERMANENT ADDRESS TAG - PER CITY AMMENDMENT. |