Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/18/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 09/17/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) THE SERVICE MUST BE PERMANENTLY ADDRESSED (NO MARKER) METAL ADDRESS TAG OK 2) MOVE ALL ITEMS FROM BELOW SERVICE TO MAINTAIN CLEARANCE 3) GROUND RODS TO BE DRIVEN TO GRADE OR BELOW ALSO CLAMPS ON RODS TO BE ALL BRASS ANY CLAMP THAT MAY CONTACT EARTH TO BE BRASS (WATER AND GAS) 4) OPEN STORAGE ROOM SO ELECTRICAL CAN BE INSPECTED-LOCKED |