Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2003 |
ELECTRIC - FINAL |
|
Approved |
1) OK TO CLEAR INCREASE SENT TO TEP ON 1009AM |
| 09/24/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) BOND BUSHINGS NEEDED BOTH SIDES OF SERVICE NIPPLE 250.94 3) PROTECT CONDUCTORS ENTERING PANEL 4) STRAP CONDUIT BELOW PANEL 5) FILL UNUSED OPENINGS IN PANEL 6) INSTALL A GROUNDING ELECTRODE SYSTEM 250.50 7) INSTALL GAS AND WATER BONDING 250.104 8) LABEL ALL BREAKERS 9) VERIFY NEW PERMIT FOR NEW A/C UNIT |