Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/26/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 0929AM |
| 08/28/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) SUPPORT 3/4" CONDUIT W/IN 3 FT OF PANELBOARD. 2) SCREW OR RIVET ADDRESS TAG TO PANEL. 3) HEDGE IN FRONT OF SERVICE TO BE COMPLETELY CLEARED PER '99 NEC 110-26. 4) DRIVE RODS FLUSH OR BELOW GRADE. 5) RE ARRANGE GROUND WIRE TO WALL AREA TO BE FIRMLY ATTACHED. |