Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO RECONNECT 2) SENT TO TEP 1015AM |
| 10/09/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ WILL NEED A LETTER BY ELECTRICAL CONTRACTOR - FOLLOW UP 5 DAYS. |
| 10/06/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE FINISH #1, 6 AND 7 OF PREVIOUS INSPECTION |
| 09/22/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) HAVE LICENSED L-11 CONTRACTOR SUBMIT LETTER OF RESPONSIBILITY FOR WORK 2) TIGHTEN LOOSE FITTING 3) FINISH TAPING SPLICE/TAP 4) DOOR TO DISCONNECT TO OPEN 90 DEGREE 5) INSTALL ACURN CLAMP CORRECTLY 2ND ROD 6) SEPERATE GROUNDS AND NEUTRAL AT 2ND PANEL 7) BOND ENCLOSURE |
| 09/03/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ NO WORK PROGRESS. WORK TO BE PERFORMED BY A L-11 ELECTRICAL CONTRACTOR. A SERVICE UPGRADE PERMIT MAY BE NEEDED. |
| 08/28/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/1) WE HAVE MULTIPLE TERMINATIONS AT LUGS. MAIN DISCONNECT. 2) LOAD CONDUCTOR ISOLATION IS DETERIORATED. 3) MAIN DISCONNECT IS IN A RUSTED CONDITION DUE TO WATER ENTERING ENCLOSURE. 4) PROPER GROUNDING AND SPLICES NEEDED FOR LOWER DISCONNECT. |
| 08/26/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE UNLOCK SERVICE DISCONNECT TO CHECK CONDITION OF DISCONNECT |