Permit: T03EL01711

Parcel: 12102008A


Addresses:

5445 E PIMA ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL01711

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO RECONNECT 2) SENT TO TEP 1015AM
10/09/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ WILL NEED A LETTER BY ELECTRICAL CONTRACTOR - FOLLOW UP 5 DAYS.
10/06/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PLEASE FINISH #1, 6 AND 7 OF PREVIOUS INSPECTION
09/22/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) HAVE LICENSED L-11 CONTRACTOR SUBMIT LETTER OF RESPONSIBILITY FOR WORK 2) TIGHTEN LOOSE FITTING 3) FINISH TAPING SPLICE/TAP 4) DOOR TO DISCONNECT TO OPEN 90 DEGREE 5) INSTALL ACURN CLAMP CORRECTLY 2ND ROD 6) SEPERATE GROUNDS AND NEUTRAL AT 2ND PANEL 7) BOND ENCLOSURE
09/03/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ NO WORK PROGRESS. WORK TO BE PERFORMED BY A L-11 ELECTRICAL CONTRACTOR. A SERVICE UPGRADE PERMIT MAY BE NEEDED.
08/28/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/1) WE HAVE MULTIPLE TERMINATIONS AT LUGS. MAIN DISCONNECT. 2) LOAD CONDUCTOR ISOLATION IS DETERIORATED. 3) MAIN DISCONNECT IS IN A RUSTED CONDITION DUE TO WATER ENTERING ENCLOSURE. 4) PROPER GROUNDING AND SPLICES NEEDED FOR LOWER DISCONNECT.
08/26/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PLEASE UNLOCK SERVICE DISCONNECT TO CHECK CONDITION OF DISCONNECT