Permit: T03EL01690

Parcel: 12112441A


Addresses:

5446 E BELLEVUE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/24/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 1027AM
09/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) PERMIT NEEDED FOR SERVICE UPGRADE TO 5446 E. BELLEVUE ST 2) PERMANENT METAL UNIT LABELS NEEDED 3) A SEALING DEVICE IS NEEDED ABOVE CURRENT CARRING PARTS4) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED TERMINAL 5) SERVICE ENTRANCE CONDUCTORS TO BE SIZED PROPERLY, THIS IS A LISTED 200 AMP METER PACK
09/04/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999* NOTHING HAS BEEN DONE SINCE INSPECTION ON 8/29/03. REFEE TO BE CHARGED IF INSPECTION CALLED BACK OUT AND WORK NOT COMPLETED.
08/29/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/1) A PERMANENT METER ADDRESS LABEL IS NEEDED. 2) BONDING DEVICES NEEDED AS PER 250-94 3) SERVICE DISCONNECT HAS MULTIPLE TERMINATIONS. 4) SERVICE IS IN A RUSTED AND DETERIORATED, UNSAFE CONDITION. 5) ENT NOT LISTED FOR OUTDOOR USE. 6) 2ND DISCONNECT IS DETACHABLE FROM SERVICE. 7) METER SOCKET ABOVE TEP REQUIREMENT OF 6'3"