Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/04/2003 |
ELECTRIC - FINAL |
|
Approved |
SENT TO TEP ON 0905AM |
| 08/29/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*/BE ADVISED: 1) UNFUSED SERVICE ENTRANCE CONDUCTORS AND LOAD CONDUCTORS CANNOT OCCUPY THE SAME SPACE. SEE NEC ARTICLE 230. 2) THE PIPE NIPPLES FROM METER CAN TO GUTTER AND AT EACH DISCONNECT MUST HAVE GROUNDING BUSHINGS. SEE ARTICLE 250 AND 300. 3) INSTALL THE BONDING SCREW, PROVIDED WITH EACH DISCONNECT, INTO THE NEUTRAL BAR AND CAN. 4) WIRE BRUSH THE WATER PIPE CLEAN OF ANY PAINT, THEN APPLY THE PIPE CLAMP. 5) BURY THE GROUND RODS 2" BELOW GRADE. 6) STRAP THE GROUND WIRE TO THE BUILDING WITH 1 HOLE 3/8" STRAPS AND ANCHORS TO WALL. 7) THE METER, GUTTER, DISCONNECTS ETC. MUST BE MOUNTED WITH 1/4" HARDWARE(MIN,) USE APPROPRIATE ANCHORS, |