Permit: T03EL01674

Parcel: 120086750


Addresses:

4714 S 12TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL01674

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/05/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK TO CLEAR. CALLED TO OFFICE FOR AFTERNOON CLEARANCE.
09/03/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0935*/ NOTES: 1) A REINSPECTION FEE IS ASSESSED. UNIT LOCKED, NO MSG FROM APPLICANT. UNIT MUST BE OPEN FOR INPSECTION AS PER NOTES OF INSP. ON 8/21/03. PLEASE PAY REFEE AT 201 N STONE, PRIOR TO FUTURE INSPECTIONS
08/25/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) NORTH WEST 1/2 OF POWER TO BUILDING DISCONNECT AT GUTTER. 2) CIRCUIT BREAKERS IN SUB PANEL NOT CORRECT TYPE THE DO NOT CLIP IN. 3) REMOVE ALL UNUSED WIRING IN GUTTER. 4) REMOVE ALL DOUBLE LUGGING AT NORTH DISCONNECT YOU NEED TO HAVE AN ELECTRICIAN CLEAN UP ITEMS ABOVE. 5) DISCONNECT ON NORHT WALL HAS MULTIPLE LUGGING AND A HOLE BELOW IT. 6) FUSING MISSING IN DISCONNECTS NORTH WALL.
08/22/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) INSTALL MISSING COVER FOR LIGHT SWITCH IS OUTSIDE RESTROOM. 2) TERMINATE MC CABLE WITH BARE WIRE IN BACK ROOM, INTO PROPER JUNCTION BOX, CAP OFF WIRING, OR ABANDON CABLE.
08/21/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0920*/ 1) NOTES: UNIT MUST BE OPEN FOR INSPECTION 2) RECALL WHEN ACCESS AVAILABLE
08/20/2003 ELECTRIC - FINAL Cancelled IVRS - Ri canceled