Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL01674
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR. CALLED TO OFFICE FOR AFTERNOON CLEARANCE. | |
09/03/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*/ NOTES: 1) A REINSPECTION FEE IS ASSESSED. UNIT LOCKED, NO MSG FROM APPLICANT. UNIT MUST BE OPEN FOR INPSECTION AS PER NOTES OF INSP. ON 8/21/03. PLEASE PAY REFEE AT 201 N STONE, PRIOR TO FUTURE INSPECTIONS | |
08/25/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) NORTH WEST 1/2 OF POWER TO BUILDING DISCONNECT AT GUTTER. 2) CIRCUIT BREAKERS IN SUB PANEL NOT CORRECT TYPE THE DO NOT CLIP IN. 3) REMOVE ALL UNUSED WIRING IN GUTTER. 4) REMOVE ALL DOUBLE LUGGING AT NORTH DISCONNECT YOU NEED TO HAVE AN ELECTRICIAN CLEAN UP ITEMS ABOVE. 5) DISCONNECT ON NORHT WALL HAS MULTIPLE LUGGING AND A HOLE BELOW IT. 6) FUSING MISSING IN DISCONNECTS NORTH WALL. | |
08/22/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) INSTALL MISSING COVER FOR LIGHT SWITCH IS OUTSIDE RESTROOM. 2) TERMINATE MC CABLE WITH BARE WIRE IN BACK ROOM, INTO PROPER JUNCTION BOX, CAP OFF WIRING, OR ABANDON CABLE. | |
08/21/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*/ 1) NOTES: UNIT MUST BE OPEN FOR INSPECTION 2) RECALL WHEN ACCESS AVAILABLE | |
08/20/2003 | ELECTRIC - FINAL | Cancelled | IVRS - Ri canceled |