Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/08/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/02/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ CORRECTIONS REQUIRED: 1) PERMANENT ADDRESS ON MAIN PANEL. DO NOT USE PENCIL, PEN OR MAGIC MARKER. 2) THE CIRCUIT BREAKERS ARE ALL 20 AMP. BUT THE WIRE CONNECTED TO EACH IS #14, WHICH IS RATED FOR 15 AMPS ONLY. CHECK EACH CIRCUIT AND USE PROPER SIZE CIRCUIT BREAKER [FOR WIRE SIZE #14 = 15 AMPS, #12 AWG = 20 AMPS, #10 AWG = 30 AMP.] THERE MUST ALSO BE A CORRECT CIRCUIT DIRECTORY/INDEX ON THE PANEL OR BY MARKING EACH CIRCUIT BREAKER. CALL FOR RE-INSPECTION WHEN CORRECTIONS ARE COMPLETED. |
| 09/03/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |