Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL01666
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
12/02/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ CORRECTIONS REQUIRED: 1) PERMANENT ADDRESS ON MAIN PANEL. DO NOT USE PENCIL, PEN OR MAGIC MARKER. 2) THE CIRCUIT BREAKERS ARE ALL 20 AMP. BUT THE WIRE CONNECTED TO EACH IS #14, WHICH IS RATED FOR 15 AMPS ONLY. CHECK EACH CIRCUIT AND USE PROPER SIZE CIRCUIT BREAKER [FOR WIRE SIZE #14 = 15 AMPS, #12 AWG = 20 AMPS, #10 AWG = 30 AMP.] THERE MUST ALSO BE A CORRECT CIRCUIT DIRECTORY/INDEX ON THE PANEL OR BY MARKING EACH CIRCUIT BREAKER. CALL FOR RE-INSPECTION WHEN CORRECTIONS ARE COMPLETED. | |
09/03/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |