Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03EL01666

Parcel: 12407099B


Addresses:

831 E 10TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL01666

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/02/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ CORRECTIONS REQUIRED: 1) PERMANENT ADDRESS ON MAIN PANEL. DO NOT USE PENCIL, PEN OR MAGIC MARKER. 2) THE CIRCUIT BREAKERS ARE ALL 20 AMP. BUT THE WIRE CONNECTED TO EACH IS #14, WHICH IS RATED FOR 15 AMPS ONLY. CHECK EACH CIRCUIT AND USE PROPER SIZE CIRCUIT BREAKER [FOR WIRE SIZE #14 = 15 AMPS, #12 AWG = 20 AMPS, #10 AWG = 30 AMP.] THERE MUST ALSO BE A CORRECT CIRCUIT DIRECTORY/INDEX ON THE PANEL OR BY MARKING EACH CIRCUIT BREAKER. CALL FOR RE-INSPECTION WHEN CORRECTIONS ARE COMPLETED.
09/03/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*