Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 08/18AM |
| 08/14/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MAINTAIN A SAFE AREA IN FORNT OF SERVICE PANEL WE HAVE A TRIPING HAZARD WITH ROCKS AND UNEVEN SURFACE WITH CONCRETE 110.26 2) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 3) SUPLEMENTAL GROUND ROD TO BE CONNECTED TO 1ST GROUND ROD SO AS NOT TO HAVE AN UNEVEN PARALLEL PATH TO GROUND |