Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/22/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/15/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ GROUND WIRE RUN THROUGH WRONG SIDE OF 'ACORN' (ROD) CLAMP. MUST BE INSERTED INTO WEDGE OF CLAMP. A RE INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION. |
| 09/08/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ INSTALL OR EXPOSE THE NEW GROUNDING ELECTRODE SYSTEM IE: THE TWO GROUND RODS. PLEASE INSTALL THE CORRECT GROUND CLAMPS FOR WATER BOND TO ACCOMODATE THE CORRECT LISTED FITTINGS. IF THE 30 AMP SINGLE POLE BREAKER FEED RECEPTACLE/ PLEASE CHANGE TO EITHER OF 15 OR 20 AMP RECEPTACLE RATING. SCREW DOWN RISER SO AS TO HAVE 2' COUPLING ENCOMPASSING MAJORITY OF THREADS. PLEASE CALL 791-5550 EXT. 1136 IF ANY QUESTIONS, BETWEEN 7:15-8:15 AM. |
| 08/27/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999$ |
| 08/25/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) BRACE OR GUY BACK RISER PER TEP AND NEC 2) EXPOSE GROUNDING ELECTRODE SYSTEM ? 3) WATER BOND CONNECTION IS SLOPPY INSTALL NEW WATER PIPE CLAMP 4) WHAT DO 30 AMP SINGLE POLE BREAKERS FEED ? PANEL SCHEDULE INDICATES RECEPTACLES 5) OFF SET NIPPLE 2" IS NOT RUN INTO 2" COUPLING PROPERLY TIGHTEN WRENCH TIGHT PER NEC 6) SECURE 1/2" EMT PER NEC (WITHIN 3' OF PANEL) |
| 08/15/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/11/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SERVICE FEEDING SUB PANEL Q 546-2097, NOT TO CODE (1999 NEC) |