Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T03EL01568
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 0829AM | |
08/26/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0210*/THE OPEN CONDUCTOR OVER ROOF MUST BE IN CONDUIT. UNIT? CORRECTIONS REQUIRED: 1) EACH UNIT MUST HAVE AN ADDRESS POSTED ON THE BUILDING. REFER TO ADDRESS REQUIREMENTS SHEET ATTACHED. NUMBER FRONT AND BACK OF EACH UNIT. 2) EACH SERVICE PANEL MUST HAVE AN ADDRESS LABEL BELOW THE METER. THE LABEL MUST BE METALLIC. PEN, PENCIL OR MAGIC MARKER ARE NOT ACCEPTABLE. 3) EACH SERVICE PANEL MUST HAVE A NEW GROUNDING SYSTEM CONSISTING OF TWO (2) 5/8" X 8' GROUND RODS, BONDING OF RODS, COLD WATER PIPE, AND GAS PIPE, GROUNDED TO THE NEUTRAL BAR IN THE LOAD CENTER. 4) THE RISER CONDUITS MUST BE SUPPORTED AT 8" BELOW PANEL AND 8" ABOVE GRADE. USE UNISTRUT AND 2 PIECE STRAPS MADE FOR THE PURPOSE. THE SIMPSON STRAPS ARE NOT ACCEPTABLE AND THE FASTENERS ARE NOT PROPERLY ANCHORED TO THE WALL. CORRECT AND RECALL |