Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 08/12/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SUPPORT CONDUIT AS PER CODE-WITHIN 8' AND EVERY 10' 2) GROUND ALL JUNCTION BOXES-SHEET METAL SCREWS NOT ACCOUNTED 3) TIGHTEN ALL LOOSE FITTINGS 4) FILL UNUSED OPENINGS IN PANEL |