Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/12/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/08/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) A GROUNDING ELECTRODE SYSTEM IS NEEDED AT 2ND STRUCTURE 250.32 2) PLEASE INSTALL ALL STRANDS UNDER TERMANAL LUG 3) RISER HARDWARE TO BE 1/4" MINIMUM 4) BOND JUNCTION BOXES 250.148 5) OK PVC IN TRENCH |