Permit: T03EL01525

Parcel: 140061330


Addresses:

3732 E DOVER SV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/06/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/04/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) SERVICE PANEL, CORRECT DOUBLE LUGGING ON 15 AMP BREAKER. 2) COVER ALL UNUSED BREAKER SLOTS. 3) GROUND WIRES NOT TO BE BOLTED TO UFER - SHOULD BE IN PANEL ON GROUND BAR. 4) 60 AMP BREAKER ON #10 WIRES SB 30 AMP. 5) AC DISCONNECT DOUBLE LUGGED. 6) SEAL HOLE ON SIDE OF MAIN PANEL. 7) RANGE RECEPTACLE S/BE IN BOX AND CORD S/B IN CONDUIT. 8) KITCHEN FIXTURE MISSING.