Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/06/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/04/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SERVICE PANEL, CORRECT DOUBLE LUGGING ON 15 AMP BREAKER. 2) COVER ALL UNUSED BREAKER SLOTS. 3) GROUND WIRES NOT TO BE BOLTED TO UFER - SHOULD BE IN PANEL ON GROUND BAR. 4) 60 AMP BREAKER ON #10 WIRES SB 30 AMP. 5) AC DISCONNECT DOUBLE LUGGED. 6) SEAL HOLE ON SIDE OF MAIN PANEL. 7) RANGE RECEPTACLE S/BE IN BOX AND CORD S/B IN CONDUIT. 8) KITCHEN FIXTURE MISSING. |