Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/03/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 0904AM |
| 08/21/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) NOTES: 2 GROUND RODS REQUIRES PER ART 250 NEC 2) BOND GAS PIPING 3) ID ALL CIRCUIT BREAKERS 250.104 4) HUB REQUIRED FOR TOP ENTRY PER MANUFACTURER INSTRUCTIONS 5) ADDRESS LABEL REQUIRED, MUST BE PERMANENT TAG 6) 2-POLE 60A BREAKER SHOULD 50A ON #8 WIRE |