Permit: T03EL01481

Parcel: 134170510


Addresses:

7417 E PRINCETON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/27/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000* SENT TO TEP ON 0828AM
08/18/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ INSPECTION CANCELLED.
07/29/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) THE CUTLER HAMMER DOUBLE POLE BREAKERS ARE NOT LISTED TO BE USED IN SIEMANS PANEL SEE INSIDE DOOR LABEL 2) THE HIGHEST BREAKER SPACE ALLOWED IS 6'-7" ? SERVICE TO HIGH 3) NOTICE TO OWNER ALL ROMEX IN SERVICE AREA HAS TO BE PHYSICALLY PROTECTED AT 8' ABOVE FINISH GRADE