Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/26/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO CLEAR 2) JUMPER AROUND GAS UNION TO OTHER PIPES |
| 08/13/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE VERIFY GAS AND WATER BONDS-NO ONE HOME, NO MESSAGE AND NO PHONE NUMBER FOR CONTRACTOR |
| 08/05/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) USE APPROVED FITTINGS AT L.B.-CHASE NIPPLE NOT APPROVED 3) AN APPROVED SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 4) PLEASE VERIFY WATER AND GAS BONDING 5) PLEASE VERIFY PERMIT FOR NEW A/C 6) SUPPORT RISER WITHIN 3' OF PANEL |