Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/25/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SEAL UNUSED OPENINGS IN PANEL 2) REMOVE SECOND PANEL COMPLETELY 3) PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR-#4 PREVIOUS |
| 07/23/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM. 2) PLEASE PROTECT BULB IN CLOSETS ABOVE SHELVES. 3) WE HAVE MORE THAN 6 THROWS OF THE HAND AT THE DISCONNECTING MEANS WITH MUTIPLE TERMINATIONS. A NEW SERVICE OR ONLY 6 THROWS OF THE HAND IS REQUIRED. 4) A LICENSED ELECTRICAL CONTRACTOR IS NEEDED TO PERFORM WORK. |