Permit: T03EL01396

Parcel: 133270710


Addresses:

8031 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
SENT TO TEP 08/08/03 915AM
08/05/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) SERVICE TO HIGH. MAXIMUM 6'-7" FOR BREAKER AND 6'-5" FOR METER 2) NEED PERMANENT METAL ADDRESS LABEL 3) MAINTAIN WORKING SPACE IN FRONT OF SERVICE
08/04/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0920*/ 1) NO MESSAGE ON IVR. PROPERTY APPEARS VACANT-WHO IS LICENSED ELECTRICAL CONTRACTOR. CANNOT ACCESS YARD FOR INSPECTION