Permit: T03EL01390

Parcel: 110150500

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL01390

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/29/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 7/30AM
07/17/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) WATER BOND TO BE TO INTERIOR PIPING 250.104 3) BREAKERS NEED TO BE LABELED 110.22 4) ENTRANCE ABOVE CURRENT CARRING PARTS TO BE SEALED WITH AN APPROVED DEVICE 373.2 5) IF A NEW 30 AMP CIRCUIT IS TO BE ADDED A SEPERATE PERMIT MAY BE NEEDED FOR NEW CIRCUIT